NSN 6110-00-213-8078
Part Details | POWER DISTRIBUTION PANEL
6110-00-213-8078 A panel designed for connecting, disconnecting and protecting power line feeders and/or direct control of specific electric devices such as lights, motors, electronic equipment, and the like. See also FUSE BOX; SWITCH BOX; DISTRIBUTION BOX; and PANEL,POWER BUS,CURCUIT BREAKER.
Alternate Parts: MILP29183, MIL-P-29183, 6002625, 6110-00-213-8078, 00-213-8078, 6110002138078, 002138078
Supply Group (FSG) | NSN Assigned | NIIN | Item Name Code (INC) |
---|---|---|---|
61 | APR 25, 1973 | 00-213-8078 | 02794 ( PANEL, POWER DISTRIBUTION ) |
REFERENCE DRAWINGS & PICTURES
Cross Reference | NSN 6110-00-213-8078
Part Number | Cage Code | Manufacturer |
---|---|---|
MIL-P-29183 | 81349 | MILITARY SPECIFICATIONSPROMULGATED BY MILITARY |
6002625 | 80091 | NAVAL FACILITIES ENGINEERING COMMAND |
Technical Data | NSN 6110-00-213-8078
Characteristic | Specifications |
---|---|
INCLOSURE FEATURE | Y ANY ACCEPTABLE |
PANEL QUANTITY | 1 |
ELECTRICAL INPUT QUANTITY | 1 |
INPUT VOLTAGE RATING | V120.0 AC AND VC480.0 AC |
INPUT FREQUENCY IN HERTZ | 60.0 |
INPUT PHASE | THREE |
ELECTRICAL OUTPUT QUANTITY | 6 |
OUTPUT VOLTAGE RATING | V120.0 AC AND VC480.0 AC |
OUTPUT FREQUENCY RATING | 60 HERTZ |
PHASE | THREE |
OVERALL HEIGHT | 36.000 INCHES MAXIMUM |
OVERALL WIDTH | 36.000 INCHES MAXIMUM |
OVERALL LENGTH | 84.000 INCHES MAXIMUM |
PANEL MATERIAL | ALUMINUM |
MOUNTING METHOD | FLOOR |
SPECIAL FEATURES | PANELBOARD ARRANGED IN HORIZONTAL CONFIGURATION W/ENCLOSURE BACK AS BOTTOM SIDE AND INCLUDE HINGED COVER ON TOPSIDE,WEATHERPROOFED,CIRCUIT BREAKERS TO BE 3-POLE W/INTERRUPTING RATINGSAT 480V AC IN ACCORDANCE W/FED-SPEC W-C-375A AMEND 4,BE CLASSES AND TRIP RATINGS CONNECTED TO 3-PHASE,1200AMPERE BUS BAR,CL 2F 100 AMP TRIP-2 EA,CL 3B 225 AMP TRIP-6 EA,CL 4B 400 AMP NON-AUTOMATIC TRIP-4 EA,CONDUIT BUSHINGS TO BE TWO-PIECE INSULATING CONFORMING TO TYPE 3,CL 1,KIND R,FED-SPEC W-C-408B IN SIZES AND QUANTITIES,2 IN-2 EA F/10 AMP CIRCUIT BREAKER CONDUCTOR,3 IN-6 EA F/225 AMP CIRCUIT BREAKER CONDUCTOR,4 IN-4 EA F/400 AMP CIRCUITBREAKER CONDUCTOR,CONDUIT BUSHINGS INSTALLED IN ENCLOSURE BOTTOM SIDE IN RELATIVE LOCATION TO CIRCUIT BREAKERS THEY ARE TO BE UTILIZED,1 GROUND TERMINAL W/SOLDERLESS LUG,SOLDERLESS LUG SHALL BE COMPATIBLE W/ALUMINUM AND COPPER AND HAVE THE CAPACITY F/1 NO. 6-AWG COPPER CONDUCTOR,CONFORMS TO PORTA-POWER PAC INC,DWG NO. 105100 OR EQUAL |
SPECIFICATION/STANDARD DATA | 81349-MIL-P-29183 GOVERNMENT SPECIFICATION |
NONDEFINITIVE SPEC/STD DATA | III TYPE AND 3 CLASS |
REFERENCE NUMBER DIFFERENTIATING CHARACTERISTICS | AS MODIFIED BY CONFIGURATION OF PANELBOARD |