NSN 5925-00-009-6341

Part Details | CIRCUIT BREAKER

5925-00-009-6341 A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see RELAY (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see RELAY-SWITCH. Excludes CIRCUIT BREAKER BOX and magneto "breaker" assemblies. See also SWITCH (as modified); and CONTROLLER.

Alternate Parts: JA3A2A3A3102, JA3-A2A3A3-10-2, JA3SA2A3A3EB01D05102, JA3S-A2A3A3-EB-01-D-05-10-2, D51948132, D5-19-4813-2, 5925-00-009-6341, 00-009-6341, 5925000096341, 000096341

Supply Group (FSG) NSN Assigned NIIN Item Name Code (INC)
59AUG 04, 197200-009-634100136 ( CIRCUIT BREAKER )
REFERENCE DRAWINGS & PICTURES

MULTIPOLE-MULTIPLE ACTUATOR TYPE

Cross Reference | NSN 5925-00-009-6341
Part Number Cage Code Manufacturer
JA3-A2A3A3-10-274193EATON CORPHEINEMANN PRODUCTS
JA3S-A2A3A3-EB-01-D-05-10-274193EATON CORPHEINEMANN PRODUCTS
D5-19-4813-281361EDGEWOOD CHEMICAL BIOLOGICAL CENTERECBC
Technical Data | NSN 5925-00-009-6341
Characteristic Specifications
POLE QUANTITY3
TERMINAL TYPE AND QUANTITY6 TAB, SOLDER LUG
RESET METHOD MANUAL
BODY STYLE MULTIPOLE-MULTIPLE ACTUATOR TYPE
CASE MATERIAL PLASTIC
MOUNTING FACILITY TYPE AND QUANTITY6 THREADED HOLE
MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
BODY LENGTH1.985 INCHES MINIMUM AND 2.015 INCHES MAXIMUM
BODY WIDTH2.245 INCHES MINIMUM AND 2.255 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.555 INCHES MINIMUM AND 1.565 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.745 INCHES MINIMUM AND 0.755 INCHES MAXIMUM
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH1.655 INCHES MINIMUM AND 1.665 INCHES MAXIMUM
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH0.745 INCHES MINIMUM AND 0.755 INCHES MAXIMUM
BOSS HEIGHT0.125 INCHES MINIMUM AND 0.135 INCHES MAXIMUM
MOUNTING SURFACE TO TERMINAL END DISTANCE1.835 INCHES MINIMUM AND 1.845 INCHES MAXIMUM
THREAD SERIES DESIGNATOR UNC
NOMINAL THREAD SIZE0.138 INCHES
THREAD QUANTITY PER INCH32
MANUAL ACTUATOR TYPE AND QUANTITY3 TOGGLE
ACTUATOR FUNCTION TRIP-RESET
ACTUATOR POSITION DESIGNATION AT EACH POLE
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT ONE, TWO, AND THREE LINKED
AUXILIARY SWITCH FUNCTION AND QUANTITY1 ALARM
SWITCH LOCATION AND POSITION DESIGNATION INTERNAL AT POLE ONE
SWITCH CONTACT ARRANGEMENT SINGLE POLE, DOUBLE THROW
SWITCH CURRENT RATING AND TYPE IN AMPS10.0 AC AND 3.0 DC
SWITCH VOLTAGE RATING AND TYPE IN VOLTS250.0 AC AND 50.0 DC
SWITCH TERMINAL TYPE TAB, SOLDER LUG
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED DUSTPROOF AND FUNGUS RESISTANT
ARC QUENCHING METHOD MAGNETIC BLOWOUT
STORAGE TYPEE ANY ACCEPTABLE
FRAGILITY FACTOR MODERATELY RUGGED